No compressor oil circuit, pumps, filters or separators reduces oil-related losses and maintenance requirements.
Two product lines built on one modular R290 platform: high-efficiency heating for industrial and district energy applications, and scalable cooling for mission-critical infrastructure.
RSE industrial chillers and heat pumps are built on a shared modular platform combining natural R290 refrigerant, oil-free centrifugal turbocompressors, gas-dynamic bearings and intelligent multi-compressor control.
High-efficiency cooling for industrial and mission-critical applications
High-efficiency heating for industrial processes, district energy and thermal infrastructure.
No compressor oil circuit, pumps, filters or separators reduces oil-related losses and maintenance requirements.
A stabilizing film of refrigerant gas supports the rotor during operation, minimizing mechanical contact, friction and wear.
Validated through more than 500,000 start-stop cycles.*
*Based on compressor manufacturer test data.
Variable-speed operation continuously adapts compressor output to actual cooling demand
Individual compressor modules are activated and speed-controlled according to actual cooling demand, allowing the system to deliver only the capacity required.
Variable-speed operation adapts output as cooling demand changes.
Capacity can be configured across multiple compressor modules.
The integrated Evikon E2630-LEL sensor continuously monitors propane concentration inside the refrigeration compartment.
The sensor is positioned at the lowest point of the refrigeration compartment, where propane may accumulate because it is heavier than air.
When predefined thresholds are reached, the control system automatically activates ventilation, generates an alarm and initiates a controlled compressor shutdown.
SST +5°C to +35°C
SDT up to +57°C
60–600 kW electrical input
SST −7°C to +35°C
SDT up to +57°C
60–600 kW electrical input
SST −15°C to +35°C
SDT up to +65°C
150–1,500 kW electrical input
Nominal cooling capacity*
Turbocompressor power
Refrigerant charge
Minimum cold-water supply temperature
| PARAMETER | VALUE |
|---|---|
| Unit type | Chiller |
| Operating mode | Cooling |
| Nominal cooling capacity | 302.3 kW |
| Cooling operating point | W10/W7 |
| Cooling-side flow rate | 25 m³/h |
| Minimum cold-water supply temperature | −7°C |
| Turbocompressor power | 60 kW |
| Nominal current | 120 A |
| Electrical connection | 400/440/460/480 V, 50/60 Hz |
| Refrigerant | R290 |
| Refrigerant charge | 8.8 kg |
| Sound power | 64 dB(A) |
| Unit weight | 1,216 kg |
428.9 kW cooling capacity ÷ 46.0 kW power input
SST 30°C / SDT 45°C
100% load · RSE 350 HP/MT chiller configuration
Actual performance depends on configuration and operating conditions.
The 9.32 figure is a calculated cooling COP at this specific test point. It is not a general heating COP or a guaranteed result across all operating conditions.
| Power level | Cooling capacity QC (kW) | Power input P (kW) | COP cooling | Heating capacity QH (kW) | Discharge temp. (°C) |
|---|---|---|---|---|---|
| 100% | 428.9 | 46.0 | 9.32 | 474.9 | 60.2 |
| 70% | 392.8 | 39.9 | 9.84 | 432.7 | 61.1 |
| 50% | 341.4 | 30.2 | 11.30 | 371.6 | 57.9 |
| 40% | 282.2 | 24.2 | 11.66 | 306.4 | 57.5 |
| 30% | 212.8 | 18.1 | 11.76 | 230.9 | 57.4 |
| Cooling capacity QC (kW) | Power input P (kW) | COP cooling | Heating capacity QH (kW) | Discharge temp. (°C) |
|---|---|---|---|---|
| Power level: 100% | ||||
| 428.9 | 46.0 | 9.32 | 474.9 | 60.2 |
| Power level: 70% | ||||
| 392.8 | 39.9 | 9.84 | 432.7 | 61.1 |
| Power level: 50% | ||||
| 341.4 | 30.2 | 11.30 | 371.6 | 57.9 |
| Power level: 40% | ||||
| 282.2 | 24.2 | 11.66 | 306.4 | 57.5 |
| Power level: 30% | ||||
| 212.8 | 18.1 | 11.76 | 230.9 | 57.4 |
RSE designs and integrates chillers, industrial heat pumps, battery energy storage and cogeneration systems for energy infrastructure.